TRANSMISSION CORPORATION OF TELANGANA LIMITED

CORPORATE TRAINING INSTITUTE

GTS COLONY : HYDERABAD - 500045 : TELANGANA : INDIA

R & D Lab

R&D Lab was established at CTI in the Year 2004.

Power Transformer is a very vital equipment in Electrical system. IS1866-2000 standard mandates that Oil samples of Transformer should be tested Once in Six months as part of Preventive Maintenance. Oil sample of every New Transformer should be tested Six to seven times in One Year.

Transformer Oil Testes include:

Physical tests:

Appearance

Flash point

IFT

Chemical test:

Acidity test

Water content test (K.F. coulometer)

Electrical test:

Electrical strength

Dielectric dissipation factor & specific resistance

Detection of incipient faults:

Dissolved gas analysis

Ageing characteristics:

Furan analysis

R&D Lab conducts following Transformer Oil tests of Power Transformers ranging from 10 MVA to 315 MVA capacities.

Equipment

Test method

Interfacial Tensio Meter

ASTMD971

Flash Point apparatus

ASTMD93

Acidity Meter

IEC 62021

K F Coulometer

IS13567

High Performance Liquid Chromatograph (HPLC)

IEC61198

Break Down Voltage

IEC60156

Tan Delta Resistivity (New)

IEC60247

Dissolved Analysis 

IEC60567

 

R&D Lab is extending services to other Power Utilities (Government & Private) on nominal payment basis.